We read 30 results from City of Plano’s 2024 water quality report. No results over a legal limit; 8 above a health goal or guideline.
Serves about 288,800 people · Water system ID TX0430007 · Read the district’s 2024 report (opens in a new tab)
Open this district in the water lookupCompare with your own test results, see the district map and get matched filters.
Results from the 2024 report
Each number is copied from the district’s report and links to the page it’s printed on. Where the report lists several plants, wells or purchased water, the highest is shown.
| Contaminant | Result | Health goal | Legal limit | What it means |
|---|---|---|---|---|
| Bromatesingle sample · range 9.19 to 9.19 · NTMWD Leonard plant · 2024 report, page 11 | 9.19 ppb | 0.1 ppb | 10 ppb | Above the health goal92x the health goal |
| Chloriteaverage · NTMWD Wylie plant · 2024 report, page 7 | 0.19 ppm | 0.05 ppm | 1 ppm | Above the health goal3.7x the health goal |
| Copper90th percentile of homes tested, 1 over the action level · Customer taps · 2024 report, page 6 | 1.01 ppm | 0.3 ppm | 1.3 ppm (action level) | Above the health goal3.4x the health goal |
| Gross beta (radioactivity)highest measured · range 5.3 to 5.3 · NTMWD Wylie plant · 2024 report, page 7 | 5.3 pCi/L | 0 pCi/L | 50 pCi/L | Above the health goalThe health goal is zero |
| Lead90th percentile of homes tested, 0 over the action level · Customer taps · 2024 report, page 6 | 2.97 ppb | 0.2 ppb | 15 ppb (action level) | Above the health goal15x the health goal |
| Manganesehighest measured · range 0.03 to 0.08 · NTMWD Wylie plant · 2024 report, page 10 | 0.08 ppm | — | 0.05 ppm guideline | Above the guideline1.6x the guideline (taste, odor or stains; not a health limit) |
| pHhighest measured · range 7.4 to 8.9 · NTMWD Wylie plant · 2024 report, page 10 | 8.9 | — | — | Outside the normal rangeAlkaline water can leave scale |
| Total dissolved solidshighest measured · range 271 to 509 · NTMWD Wylie plant · 2024 report, page 10 | 509 ppm | — | 500 ppm guideline | Above the guideline1x the guideline (taste, odor or stains; not a health limit) |
| Atrazinehighest measured · range 0.1 to 0.1 · NTMWD Wylie plant · 2024 report, page 8 | 0.1 ppb | 0.15 ppb | 3 ppb | Below the health goal |
| Bariumhighest measured · range 0.04 to 0.06 · NTMWD Wylie plant, highest of 2 sources · 2024 report, page 7 | 0.06 ppm | 2 ppm | 2 ppm | Below the health goal |
| Chloramineaverage · range 0.1 to 3.88 · Distribution system · 2024 report, page 6 | 2.53 ppm | None set | 4 ppm | Below the legal limit |
| Chloridehighest measured · range 15.4 to 95.3 · NTMWD Wylie plant · 2024 report, page 10 | 95.3 ppm | — | 250 ppm guideline | Within the guideline |
| Chlorine dioxideaverage · printed as 0.027 ppm · NTMWD Wylie plant · 2024 report, page 7 | 27 ppb | None set | 800 ppb | Below the legal limit |
| Cyanidehighest measured · range 28.5 to 128 · NTMWD Wylie plant, highest of 2 sources · 2024 report, page 7 | 128 ppb | 150 ppb | 200 ppb | Below the health goal |
| Disinfection byproducts (HAA5)highest running annual average · range 12.4 to 36.5 · Distribution system · 2024 report, page 6 | 30 ppb | None set | 60 ppb | Below the legal limit |
| Disinfection byproducts (TTHM)highest running annual average · range 20.6 to 57.3 · Distribution system · 2024 report, page 6 | 41 ppb | None set | 80 ppb | Below the legal limit |
| Fluoridehighest measured · range 0.32 to 0.71 · NTMWD Wylie plant, highest of 2 sources · 2024 report, page 7 | 0.71 ppm | 1 ppm | 4 ppm | Below the health goal |
| Nitrate (as N)highest measured · range ND to 0.36 · Distribution system · 2024 report, page 6 | 0.36 ppm | 10 ppm | 10 ppm | Below the health goal |
| Sulfatehighest measured · range 39.6 to 165 · NTMWD Wylie plant · 2024 report, page 10 | 165 ppm | — | 250 ppm guideline | Within the guideline |
| Turbidity (cloudiness)highest measured · NTMWD Wylie plant · 2024 report, page 9 | 0.93 NTU | None set | 1 NTU | Below the legal limit |
| Alkalinityhighest measured · range 56.5 to 128 · NTMWD Wylie plant · 2024 report, page 10 | 128 ppm | None set | None | No health limit |
| Bromodichloromethanehighest measured · range 7.7 to 20.4 · Distribution system · 2024 report, page 6 | 20.4 ppb | None set | None | No health limit |
| Bromoformhighest measured · range 1.15 to 2.07 · Distribution system · 2024 report, page 6 | 2.07 ppb | None set | None | No health limit |
| Calciumhighest measured · range 35.4 to 66.5 · NTMWD Wylie plant · 2024 report, page 10 | 66.5 ppm | None set | None | No health limit |
| Chloroformhighest measured · range 5.09 to 20.1 · Distribution system · 2024 report, page 6 | 20.1 ppb | None set | None | No health limit |
| Dibromochloromethanehighest measured · range 5.68 to 14.9 · Distribution system · 2024 report, page 6 | 14.9 ppb | None set | None | No health limit |
| Hardnesshighest measured · range 6.14 to 11.8 · NTMWD Wylie plant · 2024 report, page 10 | 11.8 gpg (202 ppm) | — | — | Very hard |
| Magnesiumhighest measured · range 5.88 to 9.84 · NTMWD Wylie plant · 2024 report, page 10 | 9.84 ppm | None set | None | No health limit |
| Nickelhighest measured · range 4.8 to 6.7 · printed as 0.0067 ppm · NTMWD Wylie plant · 2024 report, page 10 | 6.7 ppb | None set | None | No health limit |
| Sodiumhighest measured · range 35.5 to 88.7 · NTMWD Wylie plant · 2024 report, page 10 | 88.7 ppm | None set | None | No health limit |
Utility results describe the whole system, measured where water enters the pipes, not your tap. Your home’s plumbing can add lead or copper. 1 number we weren’t sure about is held back until a person checks.
EPA testing for PFAS and lithium
EPA’s own nationwide testing (UCMR 5) found these in City of Plano’s water between Feb 2025 and Nov 2025. These are EPA lab results, separate from the district’s report. Anything not listed was not detected.
- PFBS3.1 pptFound in 1 of 4 samples · highest resultNo federal limit in force for this one
Source: EPA UCMR 5 occurrence data. The highest single result is shown; one high sample doesn’t mean every glass is that high.
What you can do
Nothing here is an emergency notice: if the district has a violation, it must tell customers directly. If you’d like to lower these at your tap, these are the treatments that remove them, and the catalog shows the models certified for each. Ranking is by certified removal; commissions never change the order.
Disinfection byproducts
Found: Bromate, Chlorite
What removes it: Carbon block.
Lead
Found: Copper, Lead
What removes it: Reverse osmosis or Certified carbon block or RO.
Radium and uranium
Found: Gross beta (radioactivity)
What removes it: Reverse osmosis.
Sediment or cloudy water
Found: Manganese
What removes it: Oxidation filter.
Salty taste / high TDS
Found: Total dissolved solids
What removes it: Reverse osmosis.
More districts: Texas water quality · All states · Something look wrong? Tell us