We read 16 results from City of Cleburne’s 2025 water quality report. 1 result over a legal limit and 3 above a health goal or guideline.
Water system ID TX1260003 · Read the district’s 2025 report (opens in a new tab)
Open this district in the water lookupCompare with your own test results, see the district map and get matched filters.
Results from the 2025 report
Each number is copied from the district’s report and links to the page it’s printed on. Where the report lists several plants, wells or purchased water, the highest is shown.
| Contaminant | Result | Health goal | Legal limit | What it means |
|---|---|---|---|---|
| Turbidity (cloudiness)highest measured · Treatment plant · 2025 report, page 7 | 1.04 NTU | None set | 1 NTU | Over the legal limit1x the legal limit |
| Gross alpha (radioactivity)highest measured · range 1.6 to 1.6 · sampled 2023 · Treated water · 2025 report, page 7 | 1.6 pCi/L | 0 pCi/L | 15 pCi/L | Above the health goalThe health goal is zero |
| Gross beta (radioactivity)highest measured · range 6.8 to 6.8 · sampled 2023 · Treated water · 2025 report, page 7 | 6.8 pCi/L | 0 pCi/L | 50 pCi/L | Above the health goalThe health goal is zero |
| Radium (combined 226 + 228)highest measured · range 0.74 to 0.74 · sampled 2023 · Treated water · 2025 report, page 7 | 0.74 pCi/L | 0 pCi/L | 5 pCi/L | Above the health goalThe health goal is zero |
| Bariumhighest measured · range 0.04 to 0.04 · Treated water · 2025 report, page 6 | 0.04 ppm | 2 ppm | 2 ppm | Below the health goal |
| Chlorineaverage · range 0.79 to 4.9 · Distribution system · 2025 report, page 5 | 4 ppm | None set | 4 ppm | Below the legal limit |
| Chromium (total)highest measured · range 1.4 to 1.4 · Treated water · 2025 report, page 6 | 1.4 ppb | None set | 100 ppb | Below the legal limit |
| Copper90th percentile of homes tested, 0 over the action level · Customer taps · 2025 report, page 5 | 0.29 ppm | 0.3 ppm | 1.3 ppm (action level) | Below the health goal |
| Cyanidehighest measured · range 52.5 to 52.5 · Treated water · 2025 report, page 6 | 52.5 ppb | 150 ppb | 200 ppb | Below the health goal |
| Disinfection byproducts (HAA5)highest running annual average · range 30.9 to 30.9 · Distribution system (2116 Woodard) · 2025 report, page 5 | 27 ppb | None set | 60 ppb | Below the legal limit |
| Disinfection byproducts (TTHM)highest running annual average · range 47.1 to 47.1 · Distribution system (2116 Woodard) · 2025 report, page 6 | 33 ppb | None set | 80 ppb | Below the legal limit |
| Fluoridehighest measured · range 0.22 to 0.22 · Treated water · 2025 report, page 6 | 0.22 ppm | 1 ppm | 4 ppm | Below the health goal |
| Lead90th percentile of homes tested, 0 over the action level · Customer taps · 2025 report, page 5 | Not detected | 0.2 ppb | 15 ppb (action level) | Not detected |
| Nitrate (as N)highest measured · range 0.02 to 0.23 · Treated water · 2025 report, page 6 | 0.23 ppm | 10 ppm | 10 ppm | Below the health goal |
| Nitrite (as N)highest measured · range 0.04 to 0.04 · sampled 2022 · Treated water · 2025 report, page 6 | 0.04 ppm | 1 ppm | 1 ppm | Below the health goal |
| Dibromochloromethanehighest measured · range ND to 6.89 · Treated water · 2025 report, page 6 | 6.89 ppb | None set | None | No health limit |
Utility results describe the whole system, measured where water enters the pipes, not your tap. Your home’s plumbing can add lead or copper.
What you can do
Nothing here is an emergency notice: if the district has a violation, it must tell customers directly. If you’d like to lower these at your tap, these are the treatments that remove them, and the catalog shows the models certified for each. Ranking is by certified removal; commissions never change the order.
Sediment or cloudy water
Found: Turbidity (cloudiness)
What removes it: Sediment filter.
Radium and uranium
Found: Gross alpha (radioactivity), Gross beta (radioactivity), Radium (combined 226 + 228)
What removes it: Reverse osmosis.
More districts: Texas water quality · All states · Something look wrong? Tell us