Dexter Pws water quality

Updated 2026-10-22 · Missouri · Affiliate disclosure

We read 26 results from Dexter Pws’s 2025 water quality report. No results over a legal limit; 4 above a health goal or guideline.

Serves about 7,927 people · Water system ID MO4010216 · Read the district’s 2025 report (opens in a new tab)

Open this district in the water lookupCompare with your own test results, see the district map and get matched filters.

Results from the 2025 report

Each number is copied from the district’s report and links to the page it’s printed on. Where the report lists several plants, wells or purchased water, the highest is shown.

ContaminantResultHealth goalLegal limitWhat it means
Lead90th percentile of homes tested, 0 over the action level · sampled 2024 · Customer taps · 2025 report, page 22.03 ppb0.2 ppb15 ppb (action level)Above the health goal10x the health goal
Radium (combined 226 + 228)highest measured · range 2.9 to 2.9 · sampled 2024 · 2025 report, page 22.9 pCi/L0 pCi/L5 pCi/LAbove the health goalThe health goal is zero
Radium-226highest measured · range 1.3 to 1.3 · sampled 2024 · 2025 report, page 21.3 pCi/L0.05 pCi/L5 pCi/LAbove the health goal26x the health goal
Radium-228highest measured · range 1.6 to 1.6 · sampled 2024 · 2025 report, page 21.6 pCi/L0.02 pCi/L5 pCi/LAbove the health goal84x the health goal
Aluminumhighest measured · range ND to 0.01 · sampled 2024 · 2025 report, page 30.01 ppm—0.2 ppm guidelineWithin the guideline
Bariumhighest measured · range 0.08 to 0.09 · sampled 2024 · 2025 report, page 20.09 ppm2 ppm2 ppmBelow the health goal
Chloridehighest measured · range 38.7 to 49.1 · sampled 2024 · 2025 report, page 349.1 ppm—250 ppm guidelineWithin the guideline
Copper90th percentile of homes tested, 0 over the action level · sampled 2024 · Customer taps · 2025 report, page 20.25 ppm0.3 ppm1.3 ppm (action level)Below the health goal
Disinfection byproducts (HAA5)highest running annual average · range 6.25 to 6.25 · DBPDUAL-03 · 2025 report, page 26 ppbNone set60 ppbBelow the legal limit
Disinfection byproducts (TTHM)highest running annual average · range 67.7 to 67.7 · DBPDUAL-03 · 2025 report, page 268 ppbNone set80 ppbBelow the legal limit
Fluoridehighest measured · range 0.48 to 0.59 · sampled 2024 · 2025 report, page 20.59 ppm1 ppm4 ppmBelow the health goal
Ironhighest measured · range ND to 0.08 · sampled 2024 · 2025 report, page 30.08 ppm—0.3 ppm guidelineWithin the guideline
Manganesehighest measured · range ND to 0.0081 · sampled 2024 · 2025 report, page 30.0081 ppm—0.05 ppm guidelineWithin the guideline
Nitrate (as N)highest measured · range 0.01 to 0.03 · 2025 report, page 20.03 ppm10 ppm10 ppmBelow the health goal
pHhighest measured · range 7.63 to 8.17 · sampled 2024 · 2025 report, page 38.17——Normal range
Sulfatehighest measured · range 11.8 to 13.7 · sampled 2024 · 2025 report, page 313.7 ppm—250 ppm guidelineWithin the guideline
Total dissolved solidshighest measured · range 304 to 337 · sampled 2024 · 2025 report, page 3337 ppm—500 ppm guidelineWithin the guideline
Zinchighest measured · range 0.0032 to 0.0038 · sampled 2024 · 2025 report, page 30.0038 ppm—5 ppm guidelineWithin the guideline
Alkalinityhighest measured · range 258 to 264 · sampled 2024 · 2025 report, page 3264 ppmNone setNoneNo health limit
Calciumhighest measured · range 51.1 to 51.8 · sampled 2024 · 2025 report, page 351.8 ppmNone setNoneNo health limit
Hardnesshighest measured · range 11.5 to 11.6 · sampled 2024 · 2025 report, page 311.6 gpg (199 ppm)——Very hard
Lithiumhighest measured · range 34 to 88.7 · sampled 2024 · highest of 2 sources · 2025 report, page 388.7 ppbNone setNoneNo health limit
Magnesiumhighest measured · range 16.3 to 17.3 · sampled 2024 · 2025 report, page 317.3 ppmNone setNoneNo health limit
Nickelhighest measured · range 1.36 to 2.13 · printed as 0.00213 MG/L · sampled 2024 · 2025 report, page 32.13 ppbNone setNoneNo health limit
Potassiumhighest measured · range 3.72 to 5.11 · sampled 2024 · 2025 report, page 35.11 ppmNone setNoneNo health limit
Sodiumhighest measured · range 35.5 to 45.6 · sampled 2024 · 2025 report, page 345.6 ppmNone setNoneNo health limit

Utility results describe the whole system, measured where water enters the pipes, not your tap. Your home’s plumbing can add lead or copper.

EPA testing for PFAS and lithium

EPA’s own nationwide testing (UCMR 5) found these in Dexter Pws’s water between Jun 2024 and Dec 2024. These are EPA lab results, separate from the district’s report. Anything not listed was not detected.

  • Lithium88.7 ppbFound in 4 of 4 samples · highest resultAbove EPA’s health reference level of 10 ppb (a guide, not a legal limit)

Source: EPA UCMR 5 occurrence data. The highest single result is shown; one high sample doesn’t mean every glass is that high.

What you can do

Nothing here is an emergency notice: if the district has a violation, it must tell customers directly. If you’d like to lower these at your tap, these are the treatments that remove them, and the catalog shows the models certified for each. Ranking is by certified removal; commissions never change the order.

Lead

Found: Lead

What removes it: Certified carbon block or RO.

See filters that remove itWhat water filter removes lead?

Radium and uranium

Found: Radium (combined 226 + 228), Radium-226, Radium-228

What removes it: Reverse osmosis.

See filters that remove it

More districts: Missouri water quality · All states · Something look wrong? Tell us